Variable Shunt Reactors for outdoor installation for SLF02
Buyer: Energinet Eltransmission A/S
- Published
- 10 August 2026
- Procedure
- neg-w-call
- Lots
- 1
- Notice number
- 00551097-2026
- Reference
- 5a700765-45e6-4e2f-aed5-f2acf9dc2ca8
- Official source
- Official source
CPV codes
- 31170000Transformadores
- 31000000Máquinas, aparatos, equipo y productos consumibles eléctricos; iluminación
Description
Delivery of four (4) variable Shunt Reactor for outdoor installation at substation Idom-lund: Rated voltage Ur: 235 kV Power rating: 60-120 Mvar Regulation Range: 50 % or above Type of regulation: onload (OLTC) Cooling: ONAN Maximum sound power level: 80 dB(A), preferably lower, (at max. operating voltage 245 kV) Corrosion Protection: C5VH or above Max. operating voltage Umax: 245 kV Frequency: 50 Hz Short circuit level 40kA Magnetic characteristic: The core must be linear up to 1.5 times rated voltage.
Awards
| Awarded to | Amount | Date |
|---|---|---|
| BALIKESIR ELECTROMECHANIC CORP. | €19,802,724 | — |